ONLINE PARTIAL DISCHARGE SYSTEM

Partial discharges have been known to accelerate the ageing process. They cause erosion of insulating material and propagate through the treeing mechanism eventually bridging the electrodes and causing insulation breakdowns. While the Capacitance & Tan Delta tests indicate the presence of these discharges, this test records such pd signals. Online Partial Discharge test will be done using a Partial Discharge Analyser by using pre-installed couplers at rated voltage without disturbing the normal running condition of the generator

Various measurement approaches are used, either standalone or in combination, to identify potential problems within a transformer’s insulation system.

These methods include:

  • Bushing tap and bushing monitor PD sensors measuring PD via the bushing tap capacitances
  • UHF drain valve antennas are inserted into the transformer tank in service via the drain valve
  • Acoustic PD detection to determine the geometric location of PD sources within a transformer

Ultrasonic methods are particularly effective at finding surface PD and corona PD. Acoustic emissions from PD activity are normally at a frequency too high. As the PD gets worse, the frequency sometimes decreases into the audible range. Using an airborne ultrasonic microphone is the most sensitive way to detect PD where there is an air path between the source and the microphone. Contact ultrasonic sensors can be used for sealed chambers.

UHF testing is particularly useful for outdoor switchyards. UHF is an online test method, so no equipment needs to be taken out of service to perform the measurements. It can detect both surface and internal discharge so only one test is needed to find any sources of discharge within the switchyard.

 

×

Get In Touch

Contact Info

Phone number

(456) 789 10 12

(456) 789 10 15

Email address

demo@gmail.com

indusinfo@gmail.com

Address info

Prognosys EMS(P) Ltd.,
1st floor, Subishi town center,
Mokila, Shankarpalle Road,
Hyderabad, Telangana – 501203.